Los Angeles / Orange / Riverside / San Bernardino (South Coast AQMD)
No ban, but a new prime gas engine must meet 11 ppm NOx, and the whole site owes offsets from 4 tons of NOx a year (about 2 MW of gas running 24/7 on an otherwise clean site, our estimate). Rented portable generators can't power a building except in outages, repairs or remote off-grid work.
Only with a months-long air permit. Together with California.
Permitted plant: Possible (Offsets from 4 tons NOx/yr site-wide)Rentals under 12 months, no air permit: No
South Coast does not ban on-site gas at data centers. A non-emergency stationary engine must meet 11 ppmvd NOx (Rule 1110.2 Table II). Under Rule 1304(d), a new or modified facility with a potential to emit of 4 tons a year or more of NOx (or VOC, SOx, PM10) must offset its emission increase under Rule 1303(b)(2), using emission reduction credits at 1.2 to 1. Separately, Rule 1110.2(d)(2)(A) bars any portable engine generator from supplying primary or supplemental power to a facility except during unforeseen utility interruptions, maintenance and repair, and remote operations where grid power is unavailable, unless it meets the stationary-engine limits.
Permitted gas generation
A new prime gas engine needs a district permit with BACT, 11 ppm NOx, and offsets for the site's full NOx increase once the site's potential to emit reaches 4 tons a year (about 2 MW of gas running 24/7 on an otherwise clean site, our estimate).
Rentals kept under 12 months
California's portable registration can't supply a site's primary power, and South Coast's own engine rule also bars rented portable generators from powering a facility except in outages, repairs or remote off-grid work, unless the unit meets stationary-engine limits (Rule 1110.2(d)(2)). Source
Details
- Who it covers
- new and existing
- Where
- South Coast AQMD covers all of Orange County and the non-desert parts of Los Angeles, Riverside and San Bernardino counties (boundary from background knowledge; not checked against 17 CCR 60100-series in this pass)
- Status
- In force
- Effective
- November 5, 2021
- Authority
- South Coast Air Quality Management District (SCAQMD)
- Last checked
- November 8, 2026
Sources
- SCAQMD Rule 1304, Exemptions (amended Nov 5, 2021), (d)(1) and Table A primary
Any new facility that has a potential to emit equal to or more than the amounts in Table A shall offset the total amount of emission increase pursuant to Rule 1303 (b)(2). ... Nitrogen Oxides (NOx) 4
- SCAQMD Rule 1303, Requirements (amended Dec 6, 2002), (b)(2)(A) primary
Unless exempt from offsets requirements pursuant to Rule 1304, emission increases shall be offset ... Offset ratios shall be 1.2-to-1.0 for Emission Reduction Credits and 1.0-to-1.0 for allocations from the Priority Reserve
- SCAQMD Rule 1110.2 (amended Nov 1, 2019), (d)(1)(B) Table II and (d)(2)(A) primary
shall not use the portable generator for: ... (ii) Primary or supplemental power to a building, facility, stationary source, or stationary equipment, except during unforeseen interruptions of electrical power from the serving utility, maintenance and repair operations, and remote operations where grid power is unavailable.
For information only, not legal advice. Confirm with your air agency and fire marshal before you rely on it. Spot an error? Email tyler@relayenergy.us.