New Jersey
Any non-emergency engine kept over 30 days needs a state permit; 25-ton NOx line statewide.
Only with a months-long air permit.
Permitted plant: Capped (Permit; 25-ton line)Rentals under 12 months, no air permit: No
In New Jersey, a reciprocating engine that stays more than 30 days at one site is a stationary engine, and any stationary engine of 37 kW or more that generates electricity, other than an emergency generator, needs a preconstruction permit and operating certificate before it is installed. So a rented gas or diesel fleet run as bridge power needs the same permit as a permanent plant. A site that could emit 25 tons a year of NOx or VOC faces LAER and emission offsets, and every county in the state is in an ozone nonattainment area. That is about 10 MW of modern gas engines running 24/7 (our estimate). NJDEP fined DataOne in Vineland $1,072,000 on Sep 22, 2026 for running 62 unpermitted 1,982 kW gas engines as stationary engines.
Permitted gas generation
Non-emergency engines of 37 kW or more need a preconstruction permit. At 25 tpy of NOx or VOC potential, the site needs LAER and emission offsets: about 10 MW of gas engines running 24/7 (our estimate, 6-18 MW).
Rentals kept under 12 months
Any engine kept more than 30 days at one site counts as stationary and needs the same permit. The 'construction engine' exclusion (a mobile generator used until power lines arrive, 12 months or less) is untested for a running data center; we read it as construction power only. Source
Details
- Who it covers
- new and existing sites; any engine of 37 kW or more kept over 30 days
- Where
- Statewide
- Status
- In force
- Authority
- NJDEP, N.J.A.C. 7:27-8 (permits and certificates) and 7:27-18 (Emission Offset Rule)
- Last checked
- November 8, 2026
Sources
- N.J.A.C. 7:27-8 (NJDEP courtesy copy) primary
"Stationary reciprocating engine" means an internal combustion engine that is a reciprocating engine that remains for more than 30 days at a single site ... but does not include a mobile electric generator being used by the military, a locomotive engine, or a construction engine.
- N.J.A.C. 7:27-8.2(c)21 (significant sources needing a permit) primary
Any stationary reciprocating engine with a maximum rated power output of 37 kW or greater, used for generating electricity, not including emergency generators
- N.J.A.C. 7:27-18.2 (Emission Offset Rule applicability) primary
NOx 25 tons per year ... VOC 25 tons per year
- NJDEP AONOCAPA, DataOne, PEA260001-75894, Sep 22, 2026 primary
You installed sixty-two ... Natural Gas, Rated Power: 1,982 kW, stationary reciprocating engines ... without first obtaining a preconstruction permit.
- EPA Green Book, 8-Hour Ozone (2015) by county (data current Oct 31, 2026) primary
All 21 New Jersey counties listed (NY-NJ-CT or Philadelphia-Atlantic City areas), both Serious
For information only, not legal advice. Confirm with your air agency and fire marshal before you rely on it. Spot an error? Email tyler@relayenergy.us.