← Bridge Power Permit Tracker

Henrico County, VA

Zoning bars running data center generators except in power outages, testing and maintenance.

No gas route.

Permitted plant: No (Zoning limit)Rentals under 12 months, no air permit: No

Henrico County's zoning code says: "Generators for a data center must not be operated other than during emergency power outages and for testing and maintenance." Testing and maintenance may run only Monday to Friday, 10 a.m. to 4 p.m. The standard applies to data centers as a principal use and, by cross-reference, to accessory data centers serving an office or industrial use. A gas or diesel generator fleet run as bridge or primary power while a site waits for grid service is not running during a power outage, so we read the rule as barring it (our reading). The code does not address fuel cells or other non-generator sources. How the rule treats data centers built before June 10, 2025 is not stated in the sections read.

Permitted gas generation

Generators for a data center may run only during emergency power outages and for weekday daytime testing and maintenance. A permanent gas plant made of generators cannot serve as primary or bridge power (our reading of 'emergency power outages').

Rentals kept under 12 months

The standard covers any 'generators for a data center' without regard to ownership or how long they stay, so we read it as covering rented units too (our reading; the text does not name rentals). State air rules do not reach nonroad rentals kept 12 months or less (9VAC5-80-1110). Source

Details

Who it covers
all data centers (principal use, Sec. 24-4328.B) and accessory data centers (Sec. 24-4438); treatment of sites approved before Ord. 1342 not read
Where
Henrico County
Status
In force
Effective
June 10, 2025
Authority
Henrico County, VA (Board of Supervisors, Ord. No. 1342, June 10, 2025)
Last checked
November 8, 2026

Sources

Check another site Need power here? Talk to us

For information only, not legal advice. Confirm with your air agency and fire marshal before you rely on it. Spot an error? Email tyler@relayenergy.us.